P1037
Speed sampling
point 1
0
100
%
80
Percentage of motor
rated speed
P1038
Speed sampling
point 2
0
100
%
85
Percentage of motor
rated speed
P1039
Speed sampling
point 3
0
100
%
90
Percentage of motor
rated speed
P1040
Speed sampling
point 4
0
100
%
95
Percentage of motor
rated speed
P1043
Deceleration stop
speed of mechanical
parameter
identification
50
150
%
100
Percentage of motor
rated speed
P1044
Torque control
maximum time of
mechanical
parameter
identification
10
300
s
60
P1045
Mechanical
parameter
identification enable
0
1
1
0-Disable
1-Enable
If auto tuning mode is set to 1, there are four phases: no-load V/F operating, stall running,
stator resistor identification and mechanical parameters identification.
If auto tuning mode is set to 2, there are three phases: stall running, stator resistor
identification and mechanical parameters identification.
If auto tuning mode is set to 3, set motor parameters manually to acquire vector control
parameters through auto tuning.
If auto tuning mode is set to 4, motor parameters and vector control parameters are
calculated by empirical parameters.
Table 4-52 Acceleration and deceleration
ID
Parameter
Min
Max
Unit
Default
Description
P1001
Speed ramps
selection mode
0
2
0
0-HMI
1-DI
2-Communication
P1002
Speed ramps
selection
0
2
0
0-Ramp 1
1-Ramp 2
2-Ramp 3
P1003
Acceleration time of
ramp 1
1
3600
s
180
P1004
Acceleration time of
ramp 2
1
3600
s
270
P1005
Acceleration time of
ramp 3
1
3600
s
360
P1006
Deceleration time of
ramp 1
1
3600
s
450
P1007
Deceleration time of
ramp 2
1
3600
s
675