Speed
P476
t
P476
P1003/P1004/P1005
Rated speed
Fig. 4-2 S-curve
Table 4-54 Frequency skipping
ID
Parameter
Min
Max
Unit
Default
Description
P0078
Frequency skipping
point 1
100
33000
0.01Hz
1500
P0079
Frequency skipping
point 2
100
33000
0.01Hz
2500
P0080
Frequency skipping
point 3
100
33000
0.01Hz
3500
P0081
Bandwidth of
frequency skipping
point 1
0
2000
0.01Hz
0
P0082
Bandwidth of
frequency skipping
point 2
0
2000
0.01Hz
0
P0083
Bandwidth of
frequency skipping
point 3
0
2000
0.01Hz
0
P0084
Speed command
threshold
0
100
rpm
0
The frequency skipping function is used to avoid the system mechanical resonance
point.
A total of 3 frequency skipping points are configured and two parameters are required to
be configured to each skipping point, namely the frequency skipping point and frequency
skipping bandwidth, as shown in Fig. 4-3. When the reference frequency is within the
frequency skipping area, the system will automatically adjust the target frequency to the
upper limit value when speed down, or to the lower limit value when speed up.
Summary of Contents for MVF2000 Series