Table 4-9 Start-up Cabinet
ID
Parameter
Min
Max
Unit
Default
Description
P0248
Start-up cabinet
re-close waiting time
0
32000
s
60
P0285 Precharge mode
0
1
0
1- None
1-Start-up cabinet
P0286
Power-on threshold
for start-up cabinet
650
850
‰
650
Permillage of rated
input voltage
P0799
Time of startup
cabinet closing
command timeout
0
3000
0.1s
100
Table 4-10 Filter Cabinet
ID
Parameter
Min
Max
Unit
Default
Description
P0798 Filter cabinet
0
1
0
1- W/O
1-W/I
Table 4-11 Control Cabinet
ID
Parameter
Min
Max
Unit
Default
Description
P1905
Low temperature
start-up enable
0
1
0
1- Disable
1-Enable
P1909
Control cabinet
temperature adjust
enable
0
1
0
1- Disable
1-Enable
P1912
Delay time of low
temperature start-up
0
32000
0.1s
18000
Table 4-12 System Operation
ID
Parameter
Min
Max
Unit
Default
Description
P0002
Default factory
setting
0
1
0
1- No action
1-Restore factory
value
P0305
System unready
condition record
0
The user can set the system parameters of the VFD as needed.
4-2 Motor parameters
Table 4-13 Multi motor configuration
ID
Parameter
Min
Max
Unit
Default
Description
P0635
Motor selection
mode
0
2
0
0-HMI
1-DI
2-Communication
P0636 Motor selection
1
8
1