P0637
Maximum number of
motor
1
8
1
When VFD is used as a multi-split soft starter, it can drive eight motors at most. The
motor can be specified by HMI, DI or communication, and motor selection can
’t be
changed during VFD running.
Table 4-14 Motor rated parameters
ID
Parameter
Min
Max
Unit
Default
Description
P0074
Motor rated
frequency
0
65535
0.01Hz
5000
P0075 Motor rated speed
0
65535
rpm
993
P0409 Motor rated voltage
0
65535
V
6000
P0410 Motor rated current
0
65535
A
74
P0413 Motor pole number
2
65535
6
Table 4-15 Speed operation configuration
ID
Parameter
Min
Max
Unit
Default
Description
P0013
Motor rotation
direction
0
2
0
0-Forward
1-Reverse
2-Two-way
P0016
Speed reference
source
0
1
0
0-PLC
1-Analog
P0076 Minimum speed
20
1000
‰
20
P0077 Maximum speed
20
3000
‰
1000
P0085
Digital input speed
setting 1
0
65535
rpm
800
P0086
Digital input speed
setting 2
0
65535
rpm
1200
P0087
Digital input speed
setting 3
0
65535
rpm
1500
P0518
PWM turn off speed
threshold of
deceleration stop
0
100
‰
15
Thousandth ratio of
motor rated speed
P0790
Motor direction
selection mode
0
2
0
0-HMI
1-DI
2-Communication
Table 4-16 Auto tuning parameter
Summary of Contents for MVF2000 Series