The sectional area of the earthing cables must be ≥16mm² and no less than 1/2 of the
sectional area of high voltage phase wires. In addition, good earthing connection with an
earthing resistance lower than 4Ω shall be provided by the user;
The earth leakage current value shall be lower than 3.5mA AC or 10mA DC and shall
meet the safety specifications related to high leakage current equipment;
The PE of the system earthing terminal shall be earthed reliably to prevent accidents;
To avoid interference, the control signals, communication, power source cables, and
power motor cables shall be wired separately rather than in the same wiring slot; if
separate wiring is impossible, the spacing between the control, signal, communication
and power source cables, and power motor cables shall be >30cm. Parallel layout shall
be avoided.
The control signals shall use multi-core wire with a shielding layer, wherein the shielding
layer shall be earthed at both ends and shall not be too long;
The wires used to transmit different signals must be routed in a mutually-cross way, for
example AC signal and DC signal.
Do not use the same grounding wire with other power equipment or welding machine.
Each drive should be grounded independently where there are multi-drives in the same
room, series connection to the ground is forbidden.