Installation Guide
ECL Comfort 310, application A376
A376.3:
D
a
n
fo
s
s
8
7
H
2
1
1
2
.1
0
Terminal
Description
Max. load
19
Phase for alarm output
18
Alarm
4 (2) A / 230 V a.c.*
17
Not to be used
16
Not to be used
15
Not to be used
14
Phase for circulation pumps
13
P3
Heating circulation pump, ON / OFF, circuit 2
4 (2) A / 230 V a.c.*
12
P2
Heating circulation pump, ON / OFF, circuit 1
4 (2) A / 230 V a.c.*
11
P1
DHW circulation pump, ON / OFF, circuit 3
4 (2) A / 230 V a.c.*
10
Supply voltage 230 V a.c. - neutral (N)
9
Supply voltage 230 V a.c. - live (L)
8
Not to be used
7
Not to be used
6
Not to be used
5
Not to be used
4
Not to be used
3
Not to be used
2
Not to be used
1
Not to be used
* Relay contacts: 4 A for ohmic load, 2 A for inductive load
Factory established jumpers:
5 to 8, 9 to 14, L to 5 and L to 9, N to 10
Danfoss District Energy
VI.GU.B1.02
DEN-SMT/DK
25