Installation Guide
ECL Comfort 310, application A376
P heat T (heat demand)
13078
Circuit
Setting range
Factory setting
3
5 ... 40 °C
20 °C
When the desired flow temperature is above the set temperature in ‘P heat T’,
the controller automatically switches ON the circulation pump.
5 ... 40:
The circulation pump is switched ON when the desired
flow temperature is above the set value.
The valve is fully closed as long as the pump is not switched on.
P post-run
13040
Circuit
Setting range
Factory setting
3
0 ... 99 m
3 m
The circulation pump in the heating circuit can be ON for a number of
minutes (m) after heating stop (the desired flow temperature gets lower
than the setting in 'P heat T' (ID no. 12078)).
This function can utilize the remaining heat in e.g.a heat exchanger.
0:
The circulation pump stops immediately after the
heating stop.
1 ... 99:
The circulation pump is ON for the set time after the
heating stop.
Frost pr. T (frost protection temperature)
13093
Circuit
Setting range
Factory setting
3
5 ... 40 °C
10 °C
Set the desired flow temperature to protect the DHW system against frost.
5 ... 40:
Desired frost protection temperature.