Installation Guide
ECL Comfort 310, application A376
Low limit Y1 (flow / power limitation, low limit, Y-axis)
11117
Circuit
Setting range
Factory setting
1
0.0 ... 999.9 l/h
999.9 l/h
Set the flow / power limitation referring to the outdoor temperature set in
'High T out X1'.
The corresponding X coordinate is set in 'High T out X1'.
The limitation function can overrule the set 'Temp. min' of the desired
flow temperature.
Low T out X2 (flow / power limitation, low limit, X-axis)
11118
Circuit
Setting range
Factory setting
1
-60 ... 20 °C
-15 °C
Set the outdoor temperature value for the high flow / power limitation.
The corresponding Y coordinate is set in 'High limit Y2'.
High limit Y2 (flow / power limitation, high limit, Y-axis)
11116
Circuit
Setting range
Factory setting
1
0.0 ... 999.9 l/h
999.9 l/h
Set the flow / power limitation referring to the outdoor temperature set
in 'Low T out X2'.
The corresponding X coordinate is set in 'Low T out X2'.
Adapt. time (adaptation time)
11112
Circuit
Setting range
Factory setting
1
OFF / 1 ... 50 s
OFF
Controls how fast the flow / power limitation adapts to the desired
limitation.
OFF:
The control function is not influenced by the ‘Adapt.
time’.
1:
The desired temperature is adapted quickly.
50:
The desired temperature is adapted slowly.
If the ‘Adapt. time’ is too low, there is a risk of unstable control.
Filter constant
11113
Circuit
Setting range
Factory setting
1
1 ... 50
10
The actual filter dampens the flow / power input data by the set factor.
1:
Minor dampening (low filter constant)
50:
Major dampening (high filter constant)