Installation Guide
ECL Comfort 310, application A376
7.3 Flow / power limit
Please see the explanation for flow and power limit in circuit 1.
At DHW heating the flow / power limit can be set to a fixed value.
Flow / power
limitation
Limit
Desired flow
temp.
° C
Time
Actual (actual flow or power)
13110
Circuit
Setting range
Factory setting
3
Read-out only
The value is the actual flow or power based on the signal from flow / energy
meter.
Limit (limitation value)
13111
Circuit
Setting range
Factory setting
3
0.0 ... 999.9 l/h
999.9 l/h
Set the limitation value.
Adapt. time (adaptation time)
13112
Circuit
Setting range
Factory setting
3
OFF / 1 ... 50 s
OFF
Controls how fast the flow / power limitation adapts to the desired
limitation.
OFF:
The control function is not influenced by the ‘Adapt.
time’.
1:
The desired temperature is adapted quickly..
50:
The desired temperature is adapted slowly..
If the ‘Adapt. time’ is too low, there is a risk of unstable control.