Installation Guide
ECL Comfort 310, application A376
Setting
ID
Page
Factory settings in circuit(s)
1
2
3
S14 pressure — A376.9
124
Alarm high — A376.9
12614
125
2.3
Alarm low — A376.9
12615
125
0.0
Alarm time-out — A376.9
12617
125
30 s
Digital S15 — A376.9
125
Alarm value — A376.9
12636
125
0
Alarm time-out — A376.9
12637
125
30 s
Max. temp. — A376.9
125
Max. flow T— A376.9
12079
126
90 °C
Delay — A376.9
12180
126
60 s
Temp. max. (flow temp. limit, max.)
13178
127
65 °C
Temp. min. (flow temp. limit, min.)
13177
127
10 °C
Limit (return temp. limitation)
13030
128
40 °C
Infl. - max. (return temp. limitation - max. influence)
13035
128
-2.0
Infl. - min. (return temp. limitation - min. influence)
13036
128
0.0
Adapt. time (adaptation time)
13037
129
25 s
Priority (priority for return temp. limitation)
13085
129
OFF
Actual (actual flow or power)
13110
130
Adapt. time (adaptation time)
13112
130
OFF
Filter constant
13113
131
10
Input type
13109
131
OFF
Units
13115
131
l/h
Auto tuning
13173
132
OFF
Motor pr. (motor protection)
13174
132
OFF
Xp (proportional band)
13184
132
80 K
Xp actual — A376.2
133
Xp (proportional band) — A376.9
13184
133
90 K
Tn (integration time constant)
13185
133
20 s
Tn (integration time constant) — A376.9
13185
133
13 s
M run (running time of the motorized control valve) — A376.9
13186
134
15 s
M run (running time of the motorized control valve) — A376.9
13186
134
15 s
Nz (neutral zone)
13187
134
3 K
Nz (neutral zone) — A376.9
13187
134
2 K
Min. act. time (min. activation time gear motor)
13189
135
3
Min. act. time (min. activation time gear motor) — A376.9
13189
135
2
Supply T (idle) — A376.2
13097
135
OFF
Tn (idle) — A376.2
13096
135
120 s
Open time — A376.2
13094
135
4.0 s
Close time — A376.2
13095
136
2.0 s
Send desired T
13500
138
ON
P exercise (pump exercise)
13022
138
ON
M exercise (valve exercise)
13023
138
OFF
P frost T
13077
138
2 °C
P heat T (heat demand)
13078
139
20 °C
Danfoss District Energy
VI.GU.B1.02
DEN-SMT/DK
73