Installation Guide
ECL Comfort 310, application A376
A376.1, example b
Indirectly connected heating and DHW system (typically district heating).
Heating circuit 2 is connected as a sub-circuit of heating circuit 1. Alternatively, heating circuit 2 can be a floor heating circuit.
S
1
D
a
n
fo
s
s
8
7
H
2
0
9
8
.1
0
ECL 310
R6
S 3
S 5
P
2
M2
S 2
S 7
P
3
M
3
P 1
S 9
S10
M1
S 4
S 6
①
②
③
Special settings for type A376.1, example b:
Navigation:
ID no.:
Recommended setting:
Circuit 1 must be able to receive a heat demand from circuit 2:
MENU \ Settings \ Application: 'Demand offset'
11017
3 K*
Circuit 2 must be able to send its heat demand to circuit 1:
MENU \ Settings \ Application: 'Send desired T'
12500
ON
Circuit 3 should not send its heat demand to circuit 1:
MENU \ Settings \ Application: 'Send desired T'
13500
OFF
* This value is added to the heat demand value from circuit 2.