Installation Guide
ECL Comfort 310, application A376
7.0 Settings, circuit 3
7.1 Flow temperature
The ECL Comfort 310 controls the DHW temperature according to
the desired flow temperature for example under the influence of
the return temperature.
The desired DHW temperature is set in the overview display.
50.3:
Actual DHW temperature
50:
Desired DHW temperature
Actual DHW temp.
Desired DHW
temp.
Temp. max. (flow temp. limit, max.)
13178
Circuit
Setting range
Factory setting
3
10 ... 150 °C
65 °C
Choose the allowed max. flow temperature for your system.
Adjust the factory setting, if required.
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.
Temp. min. (flow temp. limit, min.)
13177
Circuit
Setting range
Factory setting
3
10 ... 150 °C
10 °C
Choose the allowed min. flow temperature for your system.
Adjust the factory setting, if required.
The setting for ‘Temp. max.’ has higher priority than ‘Temp. min.’.