Installation Guide
ECL Comfort 310, application A376
Max. flow T— A376.9
12079
Circuit
Setting range
Factory setting
2
10 ... 110 °C
90 °C
The alarm is activated when the flow temperature exceeds the set value.
Delay — A376.9
12180
Circuit
Setting range
Factory setting
2
5 ... 250 s
60 s
The alarm is activated when the flow temperature has been above the limit
set in 'Max. flow T’ for a longer time (in seconds) than the set value.
126
DEN-SMT/DK
VI.GU.B1.02
Danfoss District Energy