Installation Guide
ECL Comfort 310, application A376
Pre-stop (optimized stop time)
12026
Circuit
Setting range
Factory setting
2
OFF / ON
ON
Disable the optimized stop time.
OFF:
The optimized stop time is disabled.
ON:
The optimized stop time is enabled.
Example: Optimization of Comfort from 07:00 - 22:00
Schedule
Pre-stop OFF
Pre-stop ON
07:00
22:00
Optimization start
Optimization stop
Based on (optimization based on room / outdoor temp.)
12020
Circuit
Setting range
Factory setting
2
OUT / ROOM
OUT
The optimized start and stop time can be based on either room or outdoor
temperature.
OUT:
Optimization based on outdoor temperature. Use this
setting if the room temperature is not measured.
ROOM:
Optimization based on room temperature, if measured.
Total stop
12021
Circuit
Setting range
Factory setting
2
OFF / ON
OFF
Decide whether you want a total stop during the saving temperature period.
OFF:
No total stop. The desired flow temperature is reduced
according to:
• desired room temperature in saving mode
• auto saving
ON:
The desired flow temperature is lowered to the set value
in ‘Frost pr.’ The circulation pump is stopped but frost
protection is still active, see 'P frost T'.
Desired flow temp. °C
Total stop = ON
‘Frost pr.’
Time
Desired flow temp. °C
Total stop = OFF
‘Frost pr.’
Time
The min. flow temperature limitation ('Temp. min.') is overruled when
'Total stop' is ON.
Danfoss District Energy
VI.GU.B1.02
DEN-SMT/DK
113