Installation Guide
ECL Comfort 310, application A376
Adapt. time (adaptation time)
13037
Circuit
Setting range
Factory setting
3
OFF / 1 ... 50 s
25 s
Controls how fast the return temperature adapts to the desired return
temperature limit (I control).
OFF:
The control function is not influenced by the ‘Adapt.
time’.
1:
The desired temperature is adapted quickly.
50:
The desired temperature is adapted slowly.
The adaptation function can correct the desired flow temperature
with max. 8 K.
Priority (priority for return temp. limitation)
13085
Circuit
Setting range
Factory setting
3
OFF / ON
OFF
Choose whether the return temperature limitation should overrule the set
min. flow temperature ‘Temp. min.’ .
OFF:
The min. flow temperature limit is not overruled.
ON:
The min. flow temperature limit is overruled.
The return temperature limitation for the DHW circuit is based on the
setting in 'Limit (return temp. limitation)'.
The influence factors are set in heating circuit 1.
If the return temperature limitation value in heating circuit 1 is higher
than the return temperature limitation value in the DHW circuit, the
highest value is used.
Danfoss District Energy
VI.GU.B1.02
DEN-SMT/DK
129