Installation Guide
ECL Comfort 310, application A376
Setting
ID
Page
Factory settings in circuit(s)
1
2
3
Priority (priority for return temp. limitation)
12085
107
OFF
Actual (actual flow or power)
12110
108
Actual limit (limitation value)
12111
108
High T out X1 (flow / power limitation, high limit, X-axis)
12119
108
15 °C
Low limit Y1 (flow / power limitation, low limit, Y-axis)
12117
109
999.9
l/h
Low T out X2 (flow / power limitation, low limit, X-axis)
12118
109
-15 °C
High limit Y2 (flow / power limitation, high limit, Y-axis)
12116
109
999.9
l/h
Adapt. time (adaptation time)
12112
109
OFF
Filter constant
12113
109
10
Input type
12109
110
OFF
Units
12115
110
l/h
Auto saving (saving temp. dependent on outdoor temp.)
12011
111
-15 °C
Boost
12012
111
OFF
Ramp (reference ramping)
12013
112
OFF
Optimizer (optimizing time constant)
12014
112
OFF
Pre-stop (optimized stop time)
12026
113
ON
Based on (optimization based on room / outdoor temp.)
12020
113
OUT
Total stop
12021
113
OFF
Cut-out (limit for heating cut-out)
12179
114
20 °C
Motor pr. (motor protection)
12174
115
OFF
Xp (proportional band)
12184
115
80 K
Tn (integration time constant)
12185
115
30 s
Tn (integration time constant) — A376.9
12185
115
25 s
M run (running time of the motorized control valve)
12186
115
30 s
M run (running time of the motorized control valve) — A376.9
12186
116
120 s
Nz (neutral zone)
12187
116
3 K
Nz (neutral zone) — A376.9
12187
117
2 K
Min. act. time (min. activation time gear motor)
12189
117
10
ECA addr. (choice of Remote Control Unit)
12010
119
OFF
Send desired T
12500
119
ON
P exercise (pump exercise)
12022
119
ON
M exercise (valve exercise)
12023
119
OFF
DHW priority (closed valve / normal operation)
12052
120
OFF
P frost T
12077
120
2 °C
P heat T (heat demand)
12078
120
20 °C
P post-run
12040
120
3 m
Frost pr. T (frost protection temperature)
12093
121
10 °C
Ext. input (external override) — ECL 310
12141
121
OFF
Ext. mode (external override mode)
12142
122
COM-
FORT
Upper difference
12147
123
OFF
Lower difference
12148
123
OFF
Delay
12149
124
10 m
Lowest temp.
12150
124
30 °C
Alarm overview, in general
124
72
DEN-SMT/DK
VI.GU.B1.02