Installation Guide
ECL Comfort 310, application A376
Nz (neutral zone) — A376.9
12187
Circuit
Setting range
Factory setting
2
1 ... 9 K
2 K
Set the acceptable flow temperature deviation.
Set the neutral zone to a high value if you can accept a high
variation in flow temperature. When the actual flow temperature
is within the neutral zone, the controller does not activate the
motorized control valve.
The neutral zone is symmetrical around the desired flow temperature
value, i.e. half the value is above and half the value is below this
temperature.
Min. act. time (min. activation time gear motor)
12189
Circuit
Setting range
Factory setting
2
2 ... 50
10
The min. pulse period of 20 ms (milliseconds ) for activation of the gear
motor.
Setting example
Value x 20 ms
2
40 ms
10
200 ms
50
1000 ms
The setting should be kept as high as acceptable to increase the
lifetime of the actuator (gear motor).
Danfoss District Energy
VI.GU.B1.02
DEN-SMT/DK
117