Installation Guide
ECL Comfort 310, application A376
Infl. - max. (room temp. limitation, max.)
12182
Circuit
Setting range
Factory setting
2
-9.9 ... 0.0
-4.0
Determines how much the desired flow temperature will be influenced
(decreased) if the actual room temperature is higher than the desired room
temperature (P control).
-9.9:
The room temperature has a big influence.
0.0:
The room temperature has no influence.
Infl. - min. (room temp. limitation, min.)
12183
Circuit
Setting range
Factory setting
2
0.0 .... 9.9
0.0
Determines how much the desired flow temperature will be influenced
(increased) if the actual room temperature is lower than the desired room
temperature (P control).
0.0:
The room temperature has no influence.
9.9:
The room temperature has a big influence.