Installation Guide
ECL Comfort 310, application A376
Min. act. time (min. activation time gear motor)
11189
Circuit
Setting range
Factory setting
1
2 ... 50
10
The min. pulse period of 20 ms (milliseconds ) for activation of the gear
motor.
Setting example
Value x 20 ms
2
40 ms
10
200 ms
50
1000 ms
The setting should be kept as high as acceptable to increase the
lifetime of the actuator (gear motor).
Danfoss District Energy
VI.GU.B1.02
DEN-SMT/DK
91