Installation Guide
ECL Comfort 310, application A376
6.6 Control parameters
Motor pr. (motor protection)
12174
Circuit
Setting range
Factory setting
2
OFF / 10 ... 59 m
OFF
Prevents the controller from unstable temperature control (and resulting
actuator oscillations). This can occur at very low load. The motor protection
increases the lifetime of all involved components.
OFF:
Motor protection is not activated.
10 ... 59:
Motor protection is activated after the set activation
delay (minutes).
Recommended for heating systems with variable load.
Xp (proportional band)
12184
Circuit
Setting range
Factory setting
2
5 ... 250 K
80 K
Set the proportional band. A higher value will result in a stable but
slow control of the flow temperature.
Tn (integration time constant)
12185
Circuit
Setting range
Factory setting
2
1 ... 999 s
30 s
Set a high integration time constant to obtain a slow but stable
reaction to deviations.
A low integration time constant (in seconds) will make the
controller react fast but with less stability.
Tn (integration time constant) — A376.9
12185
Circuit
Setting range
Factory setting
2
1 ... 999 s
25 s
Set a high integration time constant (in seconds) to obtain a slow
but stable reaction to deviations.
A low integration time constant will make the controller react fast
but with less stability.
M run (running time of the motorized control valve)
12186
Circuit
Setting range
Factory setting
2
5 ... 250 s
30 s
‘M run’ is the time in seconds it takes the controlled component
to move from fully closed to fully open position. Set the ‘M run’
according to the examples or measure the running time by means
of a stop watch.
How to calculate the running time of a motorized control valve
The running time of the motorized control valve is calculated using
the following methods:
Seated valves
Running time = Valve stroke (mm) x actuator speed (sec. / mm)
Example:
5.0 mm x 15 sec. / mm = 75 sec.
Rotating valves
Running time = Turning degrees x actuator speed (sec. / degr.)
Example:
90 degr. x 2 sec. / degr. = 180 sec.
Danfoss District Energy
VI.GU.B1.02