Installation Guide
ECL Comfort 310, application A376
Alarm high — A376.9
11614
Circuit
Setting range
Factory setting
1
0.0 ... 6.0
2.3
The pressure alarm is activated when the measured signal (see 'Low X', 'High
X', 'Low Y' and 'High Y') is above the set limit.
Alarm low — A376.9
11615
Circuit
Setting range
Factory setting
1
0.0 ... 6.0
0.0
The pressure alarm is activated when the measured signal (see 'Low X', 'High
X', 'Low Y' and 'High Y') is below the set limit.
Alarm time-out — A376.9
11617
Circuit
Setting range
Factory setting
1
0 ... 240 s
30 s
The pressure alarm is activated when the measured signal has been above
or below the limits for a longer time (in seconds) than the set value.
Digital S8 — A376.9
Circuit
Setting range
Factory setting
1
Access to settings related to alarm input S8.
Alarm value — A376.9
11636
Circuit
Setting range
Factory setting
1
0 / 1
0
The alarm is based on a digital input applied to S8.
0:
The alarm function is active when a switch is closed.
1:
The alarm function is active when a switch is open.
Alarm time-out — A376.9
11637
Circuit
Setting range
Factory setting
1
0 ... 240 s
30 s
The alarm is activated when the switch has been closed or opened for a
longer time (in seconds) than the set value.
Max. temp. — A376.9
Circuit
Setting range
Factory setting
1
Access to settings related to max. flow temperature alarm.
Danfoss District Energy
VI.GU.B1.02
DEN-SMT/DK
99