Installation Guide
ECL Comfort 310, application A376
Alarm high — A376.9
12614
Circuit
Setting range
Factory setting
2
0.0 ... 6.0
2.3
The pressure alarm is activated when the measured signal (see 'Low X', 'High
X', 'Low Y' and 'High Y') is above the set limit.
Alarm low — A376.9
12615
Circuit
Setting range
Factory setting
2
0.0 ... 6.0
0.0
The pressure alarm is activated when the measured signal (see 'Low X', 'High
X', 'Low Y' and 'High Y') is below the set limit.
Alarm time-out — A376.9
12617
Circuit
Setting range
Factory setting
2
0 ... 240 s
30 s
The pressure alarm is activated when the measured signal has been above
or below the limits for a longer time (in seconds) than the set value.
Digital S15 — A376.9
Circuit
Setting range
Factory setting
2
Access to settings related to alarm input S15.
Alarm value — A376.9
12636
Circuit
Setting range
Factory setting
2
0 / 1
0
The alarm is based on a digital input applied to S15.
0:
The alarm function is active when a switch is closed.
1:
The alarm function is active when a switch is open.
Alarm time-out — A376.9
12637
Circuit
Setting range
Factory setting
2
0 ... 240 s
30 s
The alarm is activated when the switch has been closed or opened for a
longer time (in seconds) than the set value.
Max. temp. — A376.9
Circuit
Setting range
Factory setting
2
Access to settings related to max. flow temperature alarm.