Installation Guide
ECL Comfort 310, application A376
A376.3 — ECA 32:
Double-insulated (two-chamber) transformer
Terminal
Description
Max. load
49
Common terminal (connected to terminal 30 in the ECL Comfort controller)
56
Analog reference for M2 and M3
57
Not to be used
58
Not to be used
59
M1
Analog Out 1:
Motorized control valve, 0–10 V, circuit 3
47 kΩ*
60
M2
Analog Out 2:
Motorized control valve, 0–10 V, circuit 1
47 kΩ*
61
M3
Analog Out 3:
Motorized control valve, 0–10 V, circuit 2
47 kΩ*
62
Analog reference for M1
* The value must be 47 kΩ as a minimum.
Danfoss District Energy
VI.GU.B1.02
DEN-SMT/DK
33