![background image](http://html1.mh-extra.com/html/daikin/vrv-s-rxq4-5arv1/vrv-s-rxq4-5arv1_service-manual_4705206067.webp)
SiAF332111E
Control for 4/5/10/12 HP Outdoor Unit
Part 4 Functions and Control
61
1.3.2 Oil Return Control
In order to prevent the compressor from running out of oil, the oil return control is conducted to
recover oil that has flowed out from the compressor to the system side.
Oil Return Control in Cooling Operation
HTdi: Compressor discharge pipe temperature (Tdi) compensated with outdoor air temperature
Pe: Low pressure sensor detection value
Tc: High pressure equivalent saturation temperature
Te: Low pressure equivalent saturation temperature
Ts: Suction pipe temperature detected by thermistor
Starting
Conditions
Oil return control is not conducted before 2 hours have elapsed from the activation of power
supply.
After 2 hours have elapsed, oil return control starts when the following item meets the
reference value.
• Total amount of oil discharged from the compressor
(The total amount of oil discharged from the compressor is computed from Tc, Te, and
compressor loads.)
Oil return control starts every 8 hours of cumulative operation of the compressor, even if the
reference value is not met.
Oil Return Control
Outdoor unit
actuator
Electric symbol
Oil return
preparation
control
Oil return control
Control after
oil return
RXQ4ARV1
RXQ5ARV1
RXMQ
10/12ARY1
Compressor
M1C
M1C
M1C
Take the current
step as the
upper limit.
Minimum frequency
(
Low pressure
protection control)
Same as oil return
control.
Outdoor fan
M1F
M1F
M1F
M2F
Fan control
(Normal cooling)
Fan control
(Normal cooling)
Fan control
(Normal cooling)
Electronic
expansion
valve (Main)
―
—
Y1E
Fully open
Fully open
Fully open
Electronic
expansion
valve
(Injection)
―
—
Y2E
SH control
0 pulse
0 pulse
Hot gas
bypass valve
Y2S
—
―
OFF
OFF
OFF
Ending conditions
20 seconds
•
3 minutes
•
Ts – Te < 5
°
C
OR
•
3 minutes
•
Pe < 0.6 MPa
•
HTdi > 110
°
C
OR
Indoor unit actuator
Cooling oil return control
Indoor fan
Thermostat ON unit
Remote controller setting
Non-operating unit
OFF
Thermostat OFF unit
Remote controller setting
Electronic expansion valve
Thermostat ON unit
Normal opening
Non-operating unit
224 pulse
Thermostat OFF unit
Normal opening with forced thermostat ON
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...