Troubleshooting by Error Code
SiAF332111E
240
Part 6 Service Diagnosis
Reference
Reference
Reference
Reference
After replacing the compressor, perform troubleshooting on the compressor based on
CHECK 3
and
CHECK 5
.
CHECK 3
Refer to page 339.
CHECK 4
Refer to page 340.
CHECK 5
Refer to page 344.
CHECK 12
Refer to page 353.
Replace the inverter PCB
(A3P).
Replace the compressor.
YES
CHECK 4
Is the power transistor
normal?
NO
A
Replace the outdoor
unit main PCB
(A1P).
Are
the high/low
pressure measured
by the service checker the
same as the actual measured
voltage values of the
high/low pressure
sensors?
YES
NO