![background image](http://html1.mh-extra.com/html/daikin/vrv-s-rxq4-5arv1/vrv-s-rxq4-5arv1_service-manual_4705206068.webp)
Control for 4/5/10/12 HP Outdoor Unit
SiAF332111E
62
Part 4 Functions and Control
1.3.3 Pump Down Residual Control
When activating the compressor, if liquid refrigerant remains in the evaporator, the liquid enters
the compressor and dilutes oil therein resulting in a decrease in lubricity.
Therefore, pump down residual control is performed to collect refrigerant in the evaporator when
the compressor is stopped.
Pump Down Residual Control in Cooling Operation
1.3.4 Restart Standby
Restart is forced into standby to prevent the power from frequently turning on and off and to
equalize pressure in the refrigerant system.
Ta: Outdoor air temperature
1.3.5 Stop Control
Actuator operation is cleared when the system is down.
Outdoor Unit
Actuator
Electric symbol
Pump down residual
control: Step 1
Pump down residual
control: Step 2
RXQ4ARV1
RXQ5ARV1
RXMQ
10/12ARY1
Compressor
M1C
M1C
M1C
124 Hz
Minimum frequency
Outdoor fan
M1F
M1F
M1F
M2F
Fan control
Fan control
Electronic
expansion valve
(Main)
―
―
Y1E
Fully open
Fully open
Electronic
expansion valve
(Injection)
―
―
Y2E
0 pulse
0 pulse
Hot gas bypass
valve
Y2S
―
―
OFF
OFF
Ending conditions
2 seconds
2 seconds
Outdoor Unit Actuator
Electric symbol
Operation
RXQ4ARV1
RXQ5ARV1
RXMQ
10/12ARY1
Compressor
M1C
M1C
M1C
OFF
Outdoor fan
M1F
M1F
M1F
M2F
Ta > 30°C: STEP 4
Ta
30°C: OFF
Electronic expansion valve (Main)
―
―
Y1E
0 pulse
Electronic expansion valve (Injection)
―
―
Y2E
0 pulse
Hot gas bypass valve
Y2S
―
―
OFF
Ending conditions
2 minutes
Outdoor Unit Actuator
Electric symbol
Operation
RXQ4ARV1
RXQ5ARV1
RXMQ
10/12ARY1
Compressor
M1C
M1C
M1C
OFF
Outdoor fan
M1F
M1F
M1F
M2F
OFF
Electronic expansion valve (Main)
―
―
Y1E
0 pulse
Electronic expansion valve (Injection)
―
―
Y2E
0 pulse
Hot gas bypass valve
Y2S
―
―
OFF
Ending conditions
Indoor unit thermostat is turned ON.
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...