Troubleshooting by Error Code
SiAF332111E
254
Part 6 Service Diagnosis
Troubleshooting
Connect the Service Checker.
Mount a pressure gauge on the
high pressure service port.
Reset the operation, and then
restart the operation.
Stop the relevant indoor units while
the system is in cooling operation,
and then check for the liquid pipe
temperature of these indoor units
after the system is stabilized.
The liquid pipe
temperature is low
(equivalent to the evaporating
temperature).
Clean the air filters
of the indoor units.
NO
YES
NO
Replace the indoor
electronic expansion
valve.
Replace the suction pipe
thermistor.
YES
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Are the
characteristics of the
suction pipe thermistor
normal?
NO
Replace the discharge
pipe thermistor.
Are the
discharge pipe
thermistor characteristics
normal?
YES
NO
Replace the high
pressure sensor
(S1NPH).
Are the high
pressure sensor
characteristics
normal?
Service Checker
Use the Service Checker to find indoor units
operating under the following conditions:
&
• Gas pipe temperature (R3T) - Liquid pipe temperature (R2T) < 2.5°C
• Electronic expansion valve opening < 300 pulse
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...