Control for 4/5/10/12 HP Outdoor Unit
SiAF332111E
60
Part 4 Functions and Control
1.3 Special Control
1.3.1 Startup Control
This control is used to equalize the pressure in the suction and discharge sides of the
compressor prior to the compressor startup, thus reducing startup loads. Furthermore, the
inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor due to oil return or else after the startup, the
following control is made.
Pc : High pressure sensor detection value
Pe : Low pressure sensor detection value
Ta : Outdoor air temperature
Startup Control in Cooling Operation
Outdoor Unit
Actuator
Electric symbol
Pressure equalization
control prior to startup
Startup control
RXQ4ARV1
RXQ5ARV1
RXMQ
10/12ARY1
STEP 1
STEP 2
Compressor
M1C
M1C
M1C
0 Hz
Minimum
frequency
Increases 2 steps every
20 seconds from
minimum frequency until
Pc – Pe >
0.39 MPa is achieved
Outdoor fan
M1F
M1F
M1F
M2F
4/5 HP: OFF
10/12 HP: STEP 7
Ta < 20°C: OFF
Ta
20°C: STEP 4
+1 step/15 seconds
(when Pc > 2.16 MPa)
–1 step/15 seconds
(when Pc < 1.77 MPa)
Electronic
expansion
valve (Main)
—
Y1E
Y1E
0 pulse
Fully open
Fully open
Electronic
expansion
valve
(Injection)
—
—
Y2E
0 pulse
0 pulse
0 pulse
Hot gas
bypass valve
Y2S
—
—
OFF
OFF
OFF
Ending conditions
A lapse of 10
seconds
•
Pc – Pe <
0.3 MPa
•
A lapse of 1 to
5 minutes
OR
•
A lapse of
130 seconds
•
Pc – Pe >
0.39 MPa
OR
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...