Troubleshooting by Error Code
SiAF332111E
308
Part 6 Service Diagnosis
RXMQ6/8AR
The contents of individual
failures vary with sub code.
Ensure the sub code, and
then go to the following:
Conduct the test operation.
(The test operation has not
been conducted.)
U3-03
Conduct the test operation.
(Test operation failed due
to indoor unit error.)
U3-02
Check for the refrigerant
piping, and then conduct
the test operation.
U3-04
Conduct the test operation
(due to the premature end
of the test operation).
U3-05
Conduct the test operation
(due to the premature end
of the test operation).
U3-06
Check for transmission
between indoor and
outdoor units, and then
conduct the test operation.
U3-07
Check for transmission
between indoor and
outdoor units, and then
conduct the test operation.
U3-08
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Conduct the refrigerant
auto charge operation.
(The refrigerant auto
charge operation has not
been conducted.)
U3-10
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...