![background image](http://html1.mh-extra.com/html/daikin/vrv-s-rxq4-5arv1/vrv-s-rxq4-5arv1_service-manual_4705206268.webp)
Troubleshooting by Error Code
SiAF332111E
262
Part 6 Service Diagnosis
Note(s)
Reference
1. Error codes and thermistors
CHECK 11
Refer to page 350.
Error
Code
Applicable Thermistor
RXQ4/5AR
RXMQ6/8AR
RXMQ10/12AR
Electric
symbol
Connector
Electric
symbol
Connector
Electric
symbol
Connector
H9
Outdoor air thermistor
R1T
X11A
R1T
X18A
R1T
X18A
J3
Discharge pipe thermistor
R2T
X12A (Group
connector)
R21T
X19A
R21T
X29A
(Group
connector)
Compressor body thermistor
—
—
—
R8T
J5
Suction pipe thermistor
R3T
R5T
R3T
X30A (Group
connector)
—
—
Accumulator thermistor
—
—
R3T
X30A
(Group
connector)
J6
Heat exchanger deicer thermistor
R4T
—
R7T
J7
Subcooling heat exchanger liquid
pipe thermistor
—
—
R5T
R5T
J8
Heat exchanger liquid pipe
thermistor
—
—
R4T
R4T
J9
Subcooling heat exchanger gas
pipe thermistor
—
—
R6T
R6T