Troubleshooting by Error Code
SiAF332111E
302
Part 6 Service Diagnosis
The
outdoor unit main
PCB has damage.
The
system enters
standby mode before the
outdoor fan starts
rotating.
The
system enters
standby mode before
completing the startup
operation of the
compressor.
The error
U2
recurs.
NO
NO
YES
YES
NO
YES
NO
YES
Replace the outdoor unit
main PCB (A1P).
Check for wirings.
Turn ON the power supply,
and then press the ON button.
Replace the outdoor unit
main PCB (A1P).
If the outdoor unit main
PCB gets severely
damaged, the
compressor and the fan
motor may have been
damaged.
Replace the outdoor unit
main PCB (A1P).
If the outdoor unit main
PCB gets severely
damaged, check for the
compressor.
Continue operation.
The error could have
resulted from causes such
as instantaneous power
failure.
A
Is the power
transistor normal?
NO
Replace the outdoor unit
main PCB (A1P).
CHECK 4
The insulation
resistance of the fan
motor is less
than 1 M
.
NO
YES
Replace the fan motor.
If the motor gets severely
damaged, the outdoor
unit main PCB (A1P)
should also be replaced.
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...