Check
SiAF332111E
342
Part 6 Service Diagnosis
RXMQ8AR
Perform the following procedures prior to check.
(1) Power OFF.
(2) Remove all the wiring connected to the PCB where power transistors are mounted on.
Point of Measurement and Judgment Criteria
Turn OFF the power supply. Then, after a lapse of 10 minutes or more, make measurement of
resistance.
When using the analog type of multimeter,
make measurement in resistance measurement mode in the x1 k
range.
When using the digital type of multimeter, make measurement in diode check mode.
Preparation
Multimeter
Prepare the analog type of multimeter.
For the digital type of multimeter, those with
diode check function are available for the
checking.
No.
Measuring point
Judgment
Criteria
Remarks
+
–
1
P2
U
2 ~ 15 k
―
2
P2
V
3
P2
W
4
U
P2
15 k
and
more
(including ∞ )
Due to
condenser
charge and so
on, resistance
measurement
may require
some time.
5
V
P2
6
W
P2
7
N32
U
8
N32
V
9
N32
W
10
U
N32
2 ~ 15 k
―
11
V
N32
12
W
N32
No.
Measuring point
Judgment
Criteria
Remarks
+
–
1
P2
U
1.2 V and more
Due to
condenser
charge and so
on, resistance
measurement
may require
some time.
2
P2
V
3
P2
W
4
U
P2
0.3 ~ 0.7 V
―
5
V
P2
6
W
P2
7
N32
U
8
N32
V
9
N32
W
10
U
N32
1.2 V and more
Due to
condenser
charge and so
on, resistance
measurement
may require
some time.
11
V
N32
12
W
N32
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...