Field Settings for Outdoor Unit (4/5 HP Models)
SiAF332111E
116
Part 5 Field Settings and Test Operation
Press the
SET (BS2)
button and match with the LEDs No. 1 - 15, push the
RETURN (BS3)
button, and confirm the data for each setting.
Data such as addresses and number of units is expressed as binary numbers; the two ways
of expressing are as follows:
Refer to the preceding page for a list of data, etc. for No. 0 - 25.
The No. 2 Low noise / demand address is expressed as a binary number
consisting of the lower 6 digits. (0 - 63)
In the figure 1, the address is 010110 (binary number), which translates to
16 + 4 + 2 = 22 (base 10 number). In other words, the address is 22.
The number of terminal blocks for No. 12 and 13 is expressed as an 8-digit
binary number, which is the combination of four upper, and four lower
digits for No. 12 and 13 respectively. (0 - 128)
In the figure 2, the address for No. 12 is 0101, the address for No. 13 is
0110, and the combination of the two is 01010110 (binary number), which
translates to 64 + 16 + 4 + 2 = 86 (base 10 number). In other words, the
number of terminal block is 86.
l h l h l l h
16 4 1
32 8 2
Figure 1
l h h h l h l
64 16
128 32
No.12
l h h h l l h
4
1
No.13
8
2
Figure 2
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...