Field Settings for Indoor Unit
SiAF332111E
106
Part 5 Field Settings and Test Operation
1.4.24 Circulation Airflow Patterns
This setting is to change the appearance pattern of the circulation airflow direction depending
on the installation environment of the indoor unit.
Cooling
: Factory setting
1.4.25 Switching Panel Type
Change this setting depending on the type of the panel connected.
: Factory setting
1.4.26 Direct Duct Connection
This is used when "fresh air intake kit equipped with fan" is connected by duct directly. The
indoor fan carries out residual operation for 1 minute after the thermostat is stopped. (For the
purpose of preventing dust on the air filter from falling off.) When the second code No. is set to
02
: Equipped, heat reclaim ventilation fan conducts the fan residual operation by linking to
indoor unit.
: Factory setting
1.4.27 Drain Pump and Humidifier Interlock Selection
This is used to interlock the humidifier with the drain pump. When water is drained out of the
unit, this setting is unnecessary.
: Factory setting
Movement pattern
(a)
(b)
(c)
(d)
Appearance
Time
(seconds)
13 (23)-14
01: Pattern 1
120
600
120
600
02: Pattern 2
120
600
0
0
03: Pattern 3
0
0
120
600
04: Pattern 4
120
600
120
600
Indicates the horizontal flap is in the position of reducing airflow volume (where the flap is
reversed).
Mode
No.
First
Code No.
Second
Code No.
Contents
13 (23)
15
01
Standard panel
02
Designer panel
Mode
No.
First
Code No.
Second
Code No.
Contents
15 (25)
2
01
Not equipped
02
Equipped
Mode
No.
First
Code No.
Second
Code No.
Contents
15 (25)
3
01
Not interlocked
02
Interlocked
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...