Troubleshooting by Error Code
SiAF332111E
300
Part 6 Service Diagnosis
Reference
Reference
Troubleshooting
CHECK 4
Refer to page 340.
CHECK 17
Refer to page 357.
NO
NO
NO
YES
YES
YES
NO
YES
CHECK 4
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Is the power supply voltage
between L and N between
220-240 V ±10%?
Is the measured
voltage greater or equal to
220-240 VDC?
Check the power transistor.
Is the power transistor failing?
Measure voltage b and - of
the electrolytic capacitor (C+, C-)
when the compressor is operating.
Calibrate the power voltage.
Replace the fan motor (M1F).
Monitor voltage.
(Instantaneous voltage drop)
Replace the fan PCB (A1P).
Replace the outdoor unit main PCB. (A1P)
CHECK 17
Is the resistance between the phases
of the fan motor connector greater
than the standard?
Check the PCB condition.
In case of a serious failure,
compressor failure may lead to PCB
failure. Therefore, failure would
recur when replacing the PCB. To
avoid this situation, recheck whether
the compressor is grounded or
whether the wire is broken.
Moreover, check the compressor
after replacing the PCB.
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...