Field Settings for Outdoor Unit (4/5 HP Models)
Part 5 Field Settings and Test Operation
119
2.3.3 Setting Procedure of Night-Time Low Noise Operation and Demand
Control
1.
Setting mode 1 (H1P OFF)
In setting mode 2, push the
MODE (BS1)
button one time.
The system enters setting
mode 1 and the H1P goes OFF.
In setting mode 1, the H6P (In low noise operation) and the H7P (In demand control) keep
lighting.
2.
Setting mode 2 (H1P ON)
(1) In setting mode 1, push and hold the
MODE (BS1)
button for more than 5 seconds.
The system enters setting mode 2 and the H1P lights up.
(2) Push the
SET (BS2)
button several times and match the LED display with the Setting No.
you want.
(3) Push the
RETURN (BS3)
button one time, and the present setting content is displayed.
Push the
SET (BS2)
button several times and match the LED display with the setting
content (as shown on next page) you want.
(4) Push the
RETURN (BS3)
button two times.
The system returns to (1).
(5) Push the
MODE (BS1)
button one time.
The system returns to setting mode 1 and the
H1P goes OFF.
: ON : OFF
l
: Blink
)
3
(
)
2
(
)
1
(
Setting
No.
Setting
contents
Setting No. indication
Setting No. indication
Setting
contents
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
H1P H2P H3P H4P H5P H6P H7P
12
External
low noise /
demand
setting
NO
(Factory
setting)
l
YES
l
22
Night-time
low noise
setting
OFF
(Factory
setting)
Level 1
l
Level 2
l
Level 3
l
l
26
Night-time
low noise
operation
start setting
8:00 PM
l
10:00 PM
(Factory
setting)
l
12:00 AM
l
27
Night-time
low noise
operation
end setting
6:00 AM
l
7:00 AM
l
8:00 AM
(Factory
setting)
l
29
Capacity
precedence
setting
Low noise
precedence
(Factory
setting)
l
Capacity
precedence
l
30
Demand
setting 1
60% of
rated power
consumption
l
70% of
rated power
consumption
(Factory
setting)
l
80% of
rated power
consumption
l
32
Constant
demand
setting
OFF
(Factory
setting)
l
ON
l
Setting mode indication section
Setting No. indication section
Set contents indication section
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...