Troubleshooting by Error Code
SiAF332111E
206
Part 6 Service Diagnosis
5.7.2 Indoor Fan Motor Abnormality (FXFSQ-AR)
Applicable
Models
FXFSQ-AR
Error Code
A6-10
Method of Error
Detection
Detection from the current flow on the fan PCB (A1P)
Detection from the rotation speed of the fan motor in operation
Detection from the position signal of the fan motor
Detection from the current flow on the fan PCB when the fan motor starting operation
Error Decision
Conditions
An overcurrent flows
The rotation speed is less than a certain level for 6 seconds.
A position error in the fan rotor continues for 5 seconds or more.
Supposed
Causes
Clogged foreign matter
Disconnection of fan motor connectors
Fan motor lock
Defective fan motor
Defective indoor unit PCB
Troubleshooting
Connect the connector correctly.
Turn OFF the power supply and
wait for 10 minutes.
NO
Turn ON the power supply and
check the HAP lamp on the indoor
unit control PCB (A1P).
YES
NO
Replace the fan motor (M1F).
NO
YES
NO
Replace the fan motor (M1F).
Resistance
between UVW of fan
motor is unbalanced, or
short-circuited.
YES
The fan
motor connector (
∗
1) is
connected to the indoor unit
control PCB
(A1P).
Remove the foreign matter.
YES
There is a foreign
matter around the fan.
It is
possible to rotate
the fan manually when the
fan motor connector is
disconnected from the indoor
unit control PCB
(A1P).
A
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Go to the next page.
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...