Control for 4/5/10/12 HP Outdoor Unit
Part 4 Functions and Control
67
1.5 Other Control
1.5.1 Demand Control
In order to limit the power consumption, the capacity of outdoor unit is forcibly reduced by using
Demand 1 Setting. To enable this operation, additional setting of Constant Demand Setting is
required.
Demand 1 Setting
Other protection control functions have precedence over the demand control.
Level
Standard for upper limit of power consumption
Level 1
Approximately 60%
Level 2 (Factory setting)
Approximately 70%
Level 3
Approximately 80%