SiAF332111E
Outline of Control (Indoor Unit)
Part 4 Functions and Control
83
3.5 Auto Draft Reducing Control (FXFSQ-AR only)
In the case where both this control is activated and auto airflow direction control (eco full
automatic control) is set, when human presence is detected, the airflow direction is
automatically set to horizontal (P0) to reduce discomfort by direct airflow.
This control works for each airflow outlet individually.
Note: This function is inoperative for the airflow outlet where an individual airflow direction is set.
3.6 Eco Full Automatic Control (FXFSQ-AR only)
This is a generic term for the setting where both fan speed and airflow direction are set to
"Auto". For detailed control contents, refer to
Automatic Airflow Rate Control
and
Airflow
Direction Control
.
3.7 Drain Pump Control
3.7.1 Normal Operation
The float switch is ON in normal operation.
When cooling operation starts (thermostat ON), the drain pump turns ON simultaneously.
After the thermostat turns OFF, the drain pump continues to operate for another 5 minutes.
The aim of residual operation after thermostat OFF is to eliminate the dew that condenses
on the indoor heat exchanger during cooling operation.
P0
P1
P2
P3
P4
Indoor
u
nit
AIR
Flap position
(Horizontal
v
ie
w
)
P0 (horizontal)
When presence is detected
Absence continues for 5 mins
Airflow direction by auto airflow direction
Cooling: P0 or P1
Float s
w
itch
Error display
Thermostat
(r
u
nning)
OFF
OFF
O
N
O
N
O
N
OFF
Drain p
u
mp
O
N
OFF
5 min.
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...