![background image](http://html1.mh-extra.com/html/daikin/vrv-s-rxq4-5arv1/vrv-s-rxq4-5arv1_service-manual_4705206018.webp)
Specifications
SiAF332111E
12
Part 1 General Information
4. Specifications
Model Name
RXQ4ARV1
RXQ5ARV1
Power supply
1 phase, 220-240 V, 50/60 Hz
1 phase, 220-240 V, 50/60 Hz
1 Cooling capacity
kW
11.2
14.0
Casing color
Ivory white
Ivory white
Dimensions: (H × W × D)
mm
990 × 940 × 320
990 × 940 × 320
Heat exchanger
Cross fin coil
Cross fin coil
Compressor
Type
Hermetically sealed swing type
Hermetically sealed swing type
Motor output
kW
1.92
3.0
Starting method
Soft start
Soft start
Fan
Type
Propeller fan
Propeller fan
Motor output
W
200
200
Airflow rate
m³/min
76
76
Drive
Direct drive
Direct drive
Connecting
pipes
Liquid pipe
mm
9.5 (Flare connection)
9.5 (Flare connection)
Gas pipe
mm
15.9 (Flare connection)
15.9 (Flare connection)
Mass
kg
72
79
Safety devices
High pressure switch,
Fan driver overload protector,
Inverter overload protector, Fuse,
Overvoltage PCB
High pressure switch,
Fan driver overload protector,
Inverter overload protector, Fuse,
Overvoltage PCB
Capacity control
%
24-100
16-100
Refrigerant
Refrigerant name
R-410A
R-410A
Charge
kg
2.9
3.4
Control
Electronic expansion valve
Electronic expansion valve
Standard accessories
Installation manual, Operation manual,
Clamps
Installation manual, Operation manual,
Clamps
Drawing No.
4D137201
4D137201
Notes:
1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m.
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...