SiAF332111E
Field Settings for Outdoor Unit (4/5 HP Models)
Part 5 Field Settings and Test Operation
113
2.2.2 Setting Mode 2
The numbers in the No. column represent the number of times to press the
SET
(BS2)
button.
n
o
i
t
p
i
r
c
s
e
D
m
e
t
i
g
n
i
t
t
e
S
.
o
N
1
Cool / heat unified
address
COOL/HEAT selection function is not available.
Keep the default factory setting.
2
Low noise / demand
address
Address for low noise / demand operation
3
Test operation
settings
Used to conduct test operation without making changes
to the PCB and replacing the refrigerant, after the
completion of maintenance.
5
Indoor unit forced
fan H
Allows forced operation of indoor fan while unit is
stopped. (H tap)
6
Indoor unit forced
operation
Allows forced operation of indoor unit.
8
Te setting
Target evaporation temperature for cooling
12
External low noise /
demand setting
Reception of external low noise or demand signal
13
AIRNET address
Set address for AIRNET.
20
Additional refrigerant
charge operation
setting
Carries out additional refrigerant charge operation.
21
Refrigerant
recovery /
vacuuming mode
setting
Sets to refrigerant recovery or vacuuming mode.
22
Night-time low noise
setting
Sets automatic nighttime low noise operation in a simple
way.
The operating time is based on Starting Set and Ending
Set.
25
Setting of low noise
level
Sets low noise level when the low noise signal is
received.
26
Night-time low noise
operation start
setting
Sets starting time of nighttime low noise operation.
(Night-time low noise setting is also required.)
27
Night-time low noise
operation end
setting
Sets ending time of nighttime low noise operation.
(Night-time low noise setting is also required.)
28
Power transistor
check mode
∗
Check after
disconnection of
compressor wires
Used for trouble diagnosis of DC compressor. Since the
waveform of inverter is output without wiring to the
compressor, it is convenient to probe whether the
trouble comes from the compressor or PCB.
29
Capacity
precedence setting
If the capacity control is required, the low noise control
is automatically released by this setting during carrying
out low noise operation and night-time low noise
operation.
30
Demand setting 1
Changes target value of power consumption when
demand control 1 is received.
32
Constant demand
setting
Enables demand control 1 without external input.
(Effective to prevent a problem that circuit breaker of
small capacity is shut down due to large load.)
Selection of setting items
Selection of setting conditions
Press the
MODE (BS1)
button for 5
seconds and enter the setting mode
2.
Press the
SET (BS2)
button and
select a setting item according to the
LED pattern shown in the table on
the right.
↓
Press the
RETURN (BS3)
button
and decide the item. (The present
setting condition is shown.)
Press the
RETURN (BS3)
button
and return to the initial status of
setting mode 2.
∗
If you become unsure of how to
proceed, press the
MODE (BS1)
button and return to the setting
mode 1.
Press the
SET (BS2)
button and
select to the setting condition you
want.
↓
Press the
RETURN (BS3)
button and
decide the condition.
Summary of Contents for VRV S RXQ4/5ARV1
Page 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Page 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Page 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Page 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Page 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...