Troubleshooting
Part 3 – Troubleshooting
3–15
3
3
4
5
1
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Measure the temperature of
suction air and supply air.
Temperature difference =
Suction air temp. Supply air
temp.
Does
indoor unit air flow rate
down?
Is the
level of high
pressure higher than
normal level?
Temperature
difference for cooling should
be between 8 and
18 C.
Does
any frost
generate around inlet
port of indoor unit heat
exchanger or outlet port
of expansion
valve?
Possible causes as follows
* Incorrect selection of model
* Affection of direct sun
Gas shortage possibly
generates trouble.
* Clogged air filter
* Soiled heat exchanger
* Malfunction of fan motor
(Refer error code A6 .)
Possible causes as follows
* Refrigerant overcharge
* Air in refrigerant system
* Soiled heat exchanger
* Short circuit of supply air
* Disturbing item in air flow
* Malfunction of fan motor of
outdoor unit
(Refer error code E7 .)
Does the
heat load increase
after installation
of the unit?
Is the
operation current
less than specified
level?
Possible causes as follows
* Insufficient compression
of compressor
* Insufficient circulation
of refrigerant
* Faulty expansion valve
Normal.
Additional unit installation
should be considered
After vacuum drying, charge
correct amount of refrigerant.
Check each item
Check each item
Check each section
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
(S1994)
Summary of Contents for RZQ100B7W1B
Page 1: ...Service Manual ESIE05 03 RZQ71 125B8V3B RZQ100 140B7W1B Sky Air Inverter R 410A B series...
Page 2: ......
Page 10: ...ESIE05 03 viii Table of Contents 3 1 4 5...
Page 24: ...ESIE05 03 1 2 Part 1 System Outline 3 1 1 5...
Page 32: ...General Outline Outdoor Units ESIE05 03 1 10 Part 1 System Outline 3 1 1 4 5...
Page 42: ...Specifications ESIE05 03 1 20 Part 1 System Outline 3 1 1 4 5...
Page 56: ...Functional Diagrams ESIE05 03 1 34 Part 1 System Outline 3 1 1 4 5...
Page 58: ...ESIE05 03 1 36 Part 1 System Outline...
Page 70: ...Wiring Diagrams ESIE05 03 1 48 Part 1 System Outline 3 1 1 4 5...
Page 84: ...PCB Layout ESIE05 03 1 62 Part 1 System Outline 3 1 1 4 5...
Page 86: ...ESIE05 03 2 2 Part 2 Functional Description 3 1 2 5...
Page 110: ...General Functionality ESIE05 03 2 26 Part 2 Functional Description 3 1 2 4 5...
Page 150: ...ESIE05 03 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 188: ...Troubleshooting ESIE05 03 3 40 Part 3 Troubleshooting 3 1 3 4 5...
Page 264: ...Additional Checks for Troubleshooting ESIE05 03 3 116 Part 3 Troubleshooting 3 1 3 4 5...
Page 266: ...ESIE05 03 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 306: ...ESIE05 03 5 2 Part 5 Disassembly and Maintenance 3 1 5...