Field settings
ESIE05-03
4–22
Part 4 – Commissioning and Test Run
3
1
4
5
This drawing shows the position of jumper JX5 on PCB A1P.
DIP switches
The table below contains the DIP switch field settings.
BS
The table below contains the BS field setting.
DIP
switch
Label on PCB
Function
Details
DS1-1
ON/OFF
Switch emergency operation outdoor unit ON/OFF.
See page 2-6.
DS1-2
Cool / Heat
Select cooling / heating emergency operation.
See page 2-6.
DS1-3
ON/OFF
Test purposes only. Keep factory setting “OFF”.
—
DS1-4
ON/OFF
Test purposes only. Keep factory setting “OFF”.
—
BS
Label on PCB
Function
Details
BS
BS1
Cooling / fan only: Pump down
Heating: Forced defrosting function
See page 2-18.
See page 2-6.
ESIE05-03.book Page 22 Wednesday, April 6, 2005 4:09 PM
Summary of Contents for RZQ100B7W1B
Page 1: ...Service Manual ESIE05 03 RZQ71 125B8V3B RZQ100 140B7W1B Sky Air Inverter R 410A B series...
Page 2: ......
Page 10: ...ESIE05 03 viii Table of Contents 3 1 4 5...
Page 24: ...ESIE05 03 1 2 Part 1 System Outline 3 1 1 5...
Page 32: ...General Outline Outdoor Units ESIE05 03 1 10 Part 1 System Outline 3 1 1 4 5...
Page 42: ...Specifications ESIE05 03 1 20 Part 1 System Outline 3 1 1 4 5...
Page 56: ...Functional Diagrams ESIE05 03 1 34 Part 1 System Outline 3 1 1 4 5...
Page 58: ...ESIE05 03 1 36 Part 1 System Outline...
Page 70: ...Wiring Diagrams ESIE05 03 1 48 Part 1 System Outline 3 1 1 4 5...
Page 84: ...PCB Layout ESIE05 03 1 62 Part 1 System Outline 3 1 1 4 5...
Page 86: ...ESIE05 03 2 2 Part 2 Functional Description 3 1 2 5...
Page 110: ...General Functionality ESIE05 03 2 26 Part 2 Functional Description 3 1 2 4 5...
Page 150: ...ESIE05 03 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 188: ...Troubleshooting ESIE05 03 3 40 Part 3 Troubleshooting 3 1 3 4 5...
Page 264: ...Additional Checks for Troubleshooting ESIE05 03 3 116 Part 3 Troubleshooting 3 1 3 4 5...
Page 266: ...ESIE05 03 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 306: ...ESIE05 03 5 2 Part 5 Disassembly and Maintenance 3 1 5...