Error Codes: Indoor Units
ESIE05-03
3–50
Part 3 – Troubleshooting
3
1
3
4
5
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector, or parts damage may be
occurred.
Is the limit
switch's transfer
connector correctly
connected?
Are
the connectors
correctly connected to
X29A and X14A
on the PC
board?
Does the swing
flap motor swing?
Does
continuity/
no continuity
reverse?
220-240 VAC?
Connect correctly.
Turn the power supply off
once and back on, and
check whether the swing
flap motor swings when
the power supply is turned
back on.
Turn the power supply off
once and back on, and
measure the output
voltage of connector X29A
when the power supply is
turned back on.
Disconnect X14A, turn the
power supply off once and
back on, and check if the
limit switch has continuity
when the power supply is
turned back on.
No
Connect correctly.
No
Replace the indoor
unit P.C.B.
Replace the swing
flap motor.
No
No
No
Yes
Yes
Yes
Yes
Yes
ESIE05-03.book Page 50 Wednesday, April 6, 2005 4:09 PM
Summary of Contents for RZQ100B7W1B
Page 1: ...Service Manual ESIE05 03 RZQ71 125B8V3B RZQ100 140B7W1B Sky Air Inverter R 410A B series...
Page 2: ......
Page 10: ...ESIE05 03 viii Table of Contents 3 1 4 5...
Page 24: ...ESIE05 03 1 2 Part 1 System Outline 3 1 1 5...
Page 32: ...General Outline Outdoor Units ESIE05 03 1 10 Part 1 System Outline 3 1 1 4 5...
Page 42: ...Specifications ESIE05 03 1 20 Part 1 System Outline 3 1 1 4 5...
Page 56: ...Functional Diagrams ESIE05 03 1 34 Part 1 System Outline 3 1 1 4 5...
Page 58: ...ESIE05 03 1 36 Part 1 System Outline...
Page 70: ...Wiring Diagrams ESIE05 03 1 48 Part 1 System Outline 3 1 1 4 5...
Page 84: ...PCB Layout ESIE05 03 1 62 Part 1 System Outline 3 1 1 4 5...
Page 86: ...ESIE05 03 2 2 Part 2 Functional Description 3 1 2 5...
Page 110: ...General Functionality ESIE05 03 2 26 Part 2 Functional Description 3 1 2 4 5...
Page 150: ...ESIE05 03 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 188: ...Troubleshooting ESIE05 03 3 40 Part 3 Troubleshooting 3 1 3 4 5...
Page 264: ...Additional Checks for Troubleshooting ESIE05 03 3 116 Part 3 Troubleshooting 3 1 3 4 5...
Page 266: ...ESIE05 03 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 306: ...ESIE05 03 5 2 Part 5 Disassembly and Maintenance 3 1 5...