Outdoor Unit Functional Concept
ESIE05-03
2–46
Part 2 – Functional Description
3
1
2
4
5
Frequency steps
The operating frequency for the sky-air RZQ inverter units will be a value chosen from a list with fixed
frequency settings that is programmed in the unit's memory:
Step No.
Compressor operation frequency
RZQ71B
RZQ100~140B
1
38Hz
41Hz
2
41Hz
44Hz
3
44Hz
48Hz
4
48Hz
52Hz
5
52Hz
55Hz
6
57Hz
58Hz
7
62Hz
69Hz
8
67Hz
72Hz
9
73Hz
78Hz
10
79Hz
84Hz
11
85Hz
90Hz
12
91Hz
94Hz
13
97Hz
98Hz
14
103Hz
102Hz
15
109Hz
107Hz
16
116Hz
112Hz
17
122Hz
117Hz
18
128Hz
123Hz
19
134Hz
131Hz
20
141Hz
139Hz
21
148Hz
147Hz
22
155Hz
155Hz
23
162Hz
164Hz
24
169Hz
174Hz
25
177Hz
---
ESIE05-03.book Page 46 Wednesday, April 6, 2005 4:09 PM
Summary of Contents for RZQ100B7W1B
Page 1: ...Service Manual ESIE05 03 RZQ71 125B8V3B RZQ100 140B7W1B Sky Air Inverter R 410A B series...
Page 2: ......
Page 10: ...ESIE05 03 viii Table of Contents 3 1 4 5...
Page 24: ...ESIE05 03 1 2 Part 1 System Outline 3 1 1 5...
Page 32: ...General Outline Outdoor Units ESIE05 03 1 10 Part 1 System Outline 3 1 1 4 5...
Page 42: ...Specifications ESIE05 03 1 20 Part 1 System Outline 3 1 1 4 5...
Page 56: ...Functional Diagrams ESIE05 03 1 34 Part 1 System Outline 3 1 1 4 5...
Page 58: ...ESIE05 03 1 36 Part 1 System Outline...
Page 70: ...Wiring Diagrams ESIE05 03 1 48 Part 1 System Outline 3 1 1 4 5...
Page 84: ...PCB Layout ESIE05 03 1 62 Part 1 System Outline 3 1 1 4 5...
Page 86: ...ESIE05 03 2 2 Part 2 Functional Description 3 1 2 5...
Page 110: ...General Functionality ESIE05 03 2 26 Part 2 Functional Description 3 1 2 4 5...
Page 150: ...ESIE05 03 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 188: ...Troubleshooting ESIE05 03 3 40 Part 3 Troubleshooting 3 1 3 4 5...
Page 264: ...Additional Checks for Troubleshooting ESIE05 03 3 116 Part 3 Troubleshooting 3 1 3 4 5...
Page 266: ...ESIE05 03 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 306: ...ESIE05 03 5 2 Part 5 Disassembly and Maintenance 3 1 5...