Outdoor Unit Functional Concept
ESIE05-03
2–56
Part 2 – Functional Description
3
1
2
4
5
Frequency
restriction in
cooling
Heating
High outdoor ambient (overload conditions):
In heating overload conditions, the outdoor fan speed will be adapted to secure the differential
pressure between high and low pressure.
Only the fan speed will be adapted in heating overload conditions.
No adjustments to the compressor frequency will be made.
Normal control
Used indoor unit
Wall mounted indoor
Other than wall mounted
indoor
---
Upper limit
frequency
Lower limit
frequency
71
109Hz
169Hz
38Hz
100
112Hz
174Hz
41Hz
125/140
139Hz
Upper limit
frequency
Lower limit
frequency
71
109Hz
48Hz
100
112Hz
72Hz
125/140
Upper limit
frequency
Lower limit
frequency
71
109Hz
62Hz
100
112Hz
72Hz
125/140
139Hz
139Hz
Ta
≥
21°C
Ta
≥
-7°C
Ta
≤
20°C
Ta
≤
-8°C
Normal operation
Outdoor unit fan
–1 step/30 sec
Outdoor unit fan
+1 step/30 sec
•Hp-Lp < 0.39MPa
•Compression ratio
< 1.8 (RZQ71)
•Hp > 3.43MPa
OR
OR
•LP<0.05MP (RZQ71)
•LPS activates (RZQ100~140)
•&
•OR
•OR
•&
•&
•&
•HP < 2.75MPa
•Hp-Lp > 0.69MPa
•Compression ratio > 2.4 (RZQ71)
•Hp-Lp > 1.08MPa
•Compression ratio > 3.2 (RZQ71)
•Hp < 3.2MPa
•Outdoor unit fan = 8 step
•Hp-Lp > 0.59MPa
•Compression ratio > 2.2
(RZQ71)
•Hp < 3.33MPa
ESIE05-03.book Page 56 Wednesday, April 6, 2005 4:09 PM
Summary of Contents for RZQ100B7W1B
Page 1: ...Service Manual ESIE05 03 RZQ71 125B8V3B RZQ100 140B7W1B Sky Air Inverter R 410A B series...
Page 2: ......
Page 10: ...ESIE05 03 viii Table of Contents 3 1 4 5...
Page 24: ...ESIE05 03 1 2 Part 1 System Outline 3 1 1 5...
Page 32: ...General Outline Outdoor Units ESIE05 03 1 10 Part 1 System Outline 3 1 1 4 5...
Page 42: ...Specifications ESIE05 03 1 20 Part 1 System Outline 3 1 1 4 5...
Page 56: ...Functional Diagrams ESIE05 03 1 34 Part 1 System Outline 3 1 1 4 5...
Page 58: ...ESIE05 03 1 36 Part 1 System Outline...
Page 70: ...Wiring Diagrams ESIE05 03 1 48 Part 1 System Outline 3 1 1 4 5...
Page 84: ...PCB Layout ESIE05 03 1 62 Part 1 System Outline 3 1 1 4 5...
Page 86: ...ESIE05 03 2 2 Part 2 Functional Description 3 1 2 5...
Page 110: ...General Functionality ESIE05 03 2 26 Part 2 Functional Description 3 1 2 4 5...
Page 150: ...ESIE05 03 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 188: ...Troubleshooting ESIE05 03 3 40 Part 3 Troubleshooting 3 1 3 4 5...
Page 264: ...Additional Checks for Troubleshooting ESIE05 03 3 116 Part 3 Troubleshooting 3 1 3 4 5...
Page 266: ...ESIE05 03 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 306: ...ESIE05 03 5 2 Part 5 Disassembly and Maintenance 3 1 5...