Test Run and Operation Data
ESIE05-03
4–36
Part 4 – Commissioning and Test Run
3
1
4
5
3.1
General Operation Data
Guide Lines for
Optimal Operation
Condition
The operation value guide lines when operating under standard conditions (at Rated frequency) by
pushing the test run button on the remote controller are as given in the table below.
Indoor Unit Fan:
“H” Operation Compressor: Rated Frequency
High
Pressure
(Mpa)
Low
Pressure
(Mpa)
Discharge
Pipe
Temperature
(°C)
Suction
Temperature
(°C)
Indoor Unit
Side:
Differential
Between
Suction Tem-
perature and
Discharge
Temperature
(°C)
Outdoor Unit
Side:
Differential
Between
Suction Tem-
perature and
Discharge
Temperature
(°C)
Cooling
26 bar ~
34 bar
6 bar ~
10 bar
60~100
–2~10
8~18
7~12
Heating
25 bar ~
32.6 bar
5.3 bar ~
7.5 bar
60~100
–6~2
14~30
2~6
ESIE05-03.book Page 36 Wednesday, April 6, 2005 4:09 PM
Summary of Contents for RZQ100B7W1B
Page 1: ...Service Manual ESIE05 03 RZQ71 125B8V3B RZQ100 140B7W1B Sky Air Inverter R 410A B series...
Page 2: ......
Page 10: ...ESIE05 03 viii Table of Contents 3 1 4 5...
Page 24: ...ESIE05 03 1 2 Part 1 System Outline 3 1 1 5...
Page 32: ...General Outline Outdoor Units ESIE05 03 1 10 Part 1 System Outline 3 1 1 4 5...
Page 42: ...Specifications ESIE05 03 1 20 Part 1 System Outline 3 1 1 4 5...
Page 56: ...Functional Diagrams ESIE05 03 1 34 Part 1 System Outline 3 1 1 4 5...
Page 58: ...ESIE05 03 1 36 Part 1 System Outline...
Page 70: ...Wiring Diagrams ESIE05 03 1 48 Part 1 System Outline 3 1 1 4 5...
Page 84: ...PCB Layout ESIE05 03 1 62 Part 1 System Outline 3 1 1 4 5...
Page 86: ...ESIE05 03 2 2 Part 2 Functional Description 3 1 2 5...
Page 110: ...General Functionality ESIE05 03 2 26 Part 2 Functional Description 3 1 2 4 5...
Page 150: ...ESIE05 03 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 188: ...Troubleshooting ESIE05 03 3 40 Part 3 Troubleshooting 3 1 3 4 5...
Page 264: ...Additional Checks for Troubleshooting ESIE05 03 3 116 Part 3 Troubleshooting 3 1 3 4 5...
Page 266: ...ESIE05 03 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 306: ...ESIE05 03 5 2 Part 5 Disassembly and Maintenance 3 1 5...