![background image](http://html1.mh-extra.com/html/daikin/rzq100b7w1b/rzq100b7w1b_service-manual_2460009277.webp)
ESIE05-03
Field settings
Part 4 – Commissioning and Test Run
4–13
3
4
5
1
2.4
Overview of the Field Settings on the Indoor Units
Field settings
The table below contains the possible field settings of all indoor units.
Mode
No.
First
code No.
Description of the setting
Second code No.
01
02
03
04
10 or 20
0
Filter counter
Light
contamination
heavy
contamination
—
—
1
Filter type
Long
Super long
External
Oil mist
2
Remote thermistor of the
remote controller
TH1 = rem.
controller
TH1 = air
return
—
—
3
Filter display
Filter indic.
No filter indic.
—
—
11 or 21
0
Number indoor to 1 outdoor
Pair
Twin
Triple
Double twin
1
Unified or indiv. set twin
Group setting
Indiv. setting
—
—
2
Fan OFF at thermostat OFF
LL-speed
OFF
—
—
12 or 22
0
KRP1B51/52/53 X1/X2 output
Thermostat
ON
Option
Operation
Malfunction
1
EKRORO
Forced OFF
ON/OFF oper-
ation
—
—
3
Fan speed heating thermostat
OFF
LL-speed
Set speed
—
—
5
Automatic restart
Disabled
Enabled
—
—
13 or 23
0
Ceiling height setting
Normal
High
Extra high
—
≤
2.7 m
>2.7
≤
3.0 m
>3.0
≤
3.5 m
—
1
Selection of air flow direction
(setting for when a blocking
pad kit has been inst alled).
4-way flow
3-way flow
2-way flow
—
3
Horizontal discharge grill
Enabled
Disabled
—
—
4
Air flow direction adjust range
setting
Draft preven-
tion
Standard
Ceil soil pre-
vention
—
5
Field fan speed changeover air
outlet (domestic only)
Standard
Option 1
Option 2
—
6
External static pressure
Normal
High
Low
—
14 or 24
0
Additional timer to guard timer
0 s
5 s
10 s
15 s
1b
(Only in
case of
BRC1D52)
0
Permission level setting
Level 2
Level 3
—
—
1
Leave home function
Not
permitted
Permitted
—
—
2
Thermostat sensor in remote
controller (for limit operation
and leave home function only)
Use
Not use
—
—
ESIE05-03.book Page 13 Wednesday, April 6, 2005 4:09 PM
Summary of Contents for RZQ100B7W1B
Page 1: ...Service Manual ESIE05 03 RZQ71 125B8V3B RZQ100 140B7W1B Sky Air Inverter R 410A B series...
Page 2: ......
Page 10: ...ESIE05 03 viii Table of Contents 3 1 4 5...
Page 24: ...ESIE05 03 1 2 Part 1 System Outline 3 1 1 5...
Page 32: ...General Outline Outdoor Units ESIE05 03 1 10 Part 1 System Outline 3 1 1 4 5...
Page 42: ...Specifications ESIE05 03 1 20 Part 1 System Outline 3 1 1 4 5...
Page 56: ...Functional Diagrams ESIE05 03 1 34 Part 1 System Outline 3 1 1 4 5...
Page 58: ...ESIE05 03 1 36 Part 1 System Outline...
Page 70: ...Wiring Diagrams ESIE05 03 1 48 Part 1 System Outline 3 1 1 4 5...
Page 84: ...PCB Layout ESIE05 03 1 62 Part 1 System Outline 3 1 1 4 5...
Page 86: ...ESIE05 03 2 2 Part 2 Functional Description 3 1 2 5...
Page 110: ...General Functionality ESIE05 03 2 26 Part 2 Functional Description 3 1 2 4 5...
Page 150: ...ESIE05 03 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 188: ...Troubleshooting ESIE05 03 3 40 Part 3 Troubleshooting 3 1 3 4 5...
Page 264: ...Additional Checks for Troubleshooting ESIE05 03 3 116 Part 3 Troubleshooting 3 1 3 4 5...
Page 266: ...ESIE05 03 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 306: ...ESIE05 03 5 2 Part 5 Disassembly and Maintenance 3 1 5...