Field Settings
SiENBE04-925_A
270
Trial Operation and Field Settings
2.3
Jumper and Switch Settings
For the location of the jumper, refer to the following pages.
Indoor unit; page 9
Outdoor unit; page 12, 14, 16
For the location of the switch, refer to page 18.
Jumper
Function
When connected
(factory set)
When cut
JB
(on indoor unit PCB)
Fan speed setting
when compressor
stops for thermostat
OFF.
(effective only at
cooling operation)
Fan speed setting ;
Remote control
setting
Fan rpm is set to “0”
<Fan stop>
JC
(on indoor unit PCB)
Power failure
recovery function
Auto-restart
The unit does not resume
operation after recovering from
a power failure. Timer ON/OFF
settings are cleared.
J5
(on outdoor unit PCB of
20/25 class)
Improvement of
defrost
performance
Standard control
Reinforced control
(ex. The frequency increases,
the duration time of defrost
lengthens.)
Switch
Function
OFF (factory set)
ON
SW4-C
(on outdoor unit PCB
of 35 class)
Improvement of
defrost
performance
Standard control
Reinforced control (ex. The
frequency increases, the
duration time of defrost
lengthens.)
SIENBE04-925_A_FRONT.pdf 285
24/02/2011 13:54:20
Summary of Contents for RXL25G2V1B
Page 8: ...SiENBE04 925_A vi Table of Contents ...
Page 14: ...Introduction SiENBE04 925_A xii ...
Page 15: ...SiENBE04 925_A List of Functions 1 Part 1 List of Functions 1 Functions 2 ...
Page 17: ...SiENBE04 925_A Specifications 3 Part 2 Specifications 1 Specifications 4 ...
Page 20: ...Specifications SiENBE04 925_A 6 Specifications ...