SiENBE04-925_A
Outdoor Unit - RXL25G2V1B
Removal Procedure
219
11
Disconnect the relay
connector for the
compressor.
12
Disconnect the 2
connectors for the
reactor.
13
Release the discharge
pipe thermistor.
Be careful not to lose the clip
for the thermistor.
14
Detach the clamp for
the thermistors from the
electrical box.
Step
Procedure
Points
(R0259)
(R0260)
(R12197
Discharge
pipe thermistor
(R12279)
Clip
(R0262)
(R12196)